8/4/2023 0 Comments Ecotect analysis autodeskIt makes it even more difficult when your model is at an angle, as the analysis grid will not quite match up the building, with "teeth" and edges.ģ. I think some of the nodes are actually on the outside of the building it is hard to see, but if any nodes can see the outside, then they will pick up these high values. The issue you were having with some light coming into your space is, I believe, caused by the analysis grid itself. I am working on a scripts that could hopefully allow the user to "clean up" their model and get rid of the extra pane, but not yet there.Ģ. I know it is somewhat painful to have to delete these double window pane as most CAD software will export the entire assembly that includes the two (actually 6) panes. If you want your glazing to be 60% VT and you are modeling two window panes, then you should make each window pane with a VT = 77.45%, so that doubling this would give you a cumulative 60% VT for each assembly. Your glazing objects are doubled - we have discussed this in a separate post - so that your VT is actually not quite correct. I have had a look at your model and in general, it looks fine and I was able to run a acceptable Radiance pass at it but there were a few items that would require your attentions for better results:ġ.